System Parameter
|
Working Temperature
|
-20 ℃~50 ℃ (derate the output if it exceeds 50 ℃, and shut down if it exceeds 70 ℃)
|
Height
|
≤ 2000m (over 2000m, derate according to GB/T3859.2)
|
Relative humidity
|
5%~95%
|
Maximum efficiency
|
94%
|
Power factor
|
± 0.99 (full load)
|
THDI
|
<5% (full load)
|
Voltage stabilization accuracy
|
<±0.5%
|
Steady current accuracy
|
<±1%
|
Output voltage setting error
|
<±0.5%
|
Output current setting error
|
<±1%
|
Start input impulse current
|
≤ 110% of rated input current
|
Voltage limiting characteristics
|
During steady current operation, if the DC output voltage exceeds the set value, the increase in output voltage is automatically limited and the state is switched to steady state
|
Current limiting characteristics
|
During steady state operation, if the DC output current exceeds the set value, the increase in output current is automatically limited and the state is switched to steady state
|
Wiring mode
|
3P3W
|
Installation method
|
Rack
|
Protection level
|
IP21
|
Cooling method
|
Forced air cooling (forward air, rear air outlet)
|
Noise
|
≤65dB
|
Communication method
|
CAN
|